Requirements for 100kW PCS Inverter
Nature: Bidirectional (charge/discharge) 3 phases grid connected Communication via modbus RTU or preferrably modbus TCP. Can be used with multiple PCS in parallel to deliver x100kW to the grid.
Functions: Supports peak shaving, load shifting (self cons.), off-grid switching. Supports Indian grid codes (configurability). Supports Island mode (grid formation, no need to be connected to the grid to start-up).
AC side: Nominal output power: 100kW on AC side. 50 Hz grid
DC side: Voltage range: 2.5 x 240 = 600V 3.65 x 240 = 876V The inverter voltage range shall cover [600 - 876] V in order to use 20 modules in series while using the full SOC span of the LFP cells.